Inverter Phases Max. output Max. output over-
current protection
Fronius Primo 3.0-1 1 3000 W 1 x C 63 A
Fronius Primo 3.5-1 1 3500 W 1 x C 63 A
Fronius Primo 3.6-1 1 3600 W 1 x C 63 A
Fronius Primo 4.0-1 1 4000 W 1 x C 63 A
Fronius Primo 4.6-1 1 4600 W 1 x C 63 A
Fronius Primo 5.0-1
AUS
1 5000 W 1 x C 63 A
Fronius Primo 5.0-1 1 5000 W 1 x C 63 A
Fronius Primo 5.0-1 SC 1 5000 W 1 x C 63 A
Fronius Primo 6.0-1 1 6000 W 1 x C 63 A
Fronius Primo 8.2-1 1 8200 W 1 x C 63 A
NOTE!
Local regulations, the energy company or other factors may require a residual
current protective device (RCD) in the AC connection lead.
For this situation, a type A residual current protective device is generally ad-
equate. In particular cases, and depending on local factors, however, the type A
residual current protective device may trip at the wrong time.
For this reason, Fronius recommends that an RCD suitable for frequency con-
verters be used.
19