2-7
Section 2 Specifications
3) Characteristic curve for the input range of 0 to 10 V
4) Characteristic curve for the input range of -10 to 10 V
2-3 Conversion Characteristics
Analog input voltage (V)
Digital output value
(INT type)
(10250) 16400
(10000) 16000
Practicable digital
output range
-400 (-250)
-0.25
10 10.25
(Note)
Gain value
Offset value
0
Analog input voltage (V)
Digital output value
(INT type)
(10125) 8200
(10000) 8000
Practicable digital
output range
-8000 (0)
-8200 (-125)
-10.25 -10
10 10.25
(Note)
Gain value
Offset value
0
Note: Parenthesized figures mean the values when the unit of digital output value is % in Fixed Range Operation mode (excl.
NP1AWH6-MR). In software Set Range Operation mode, scaling is necessary to express output values by the %.