4-27
Section 4 Software Interface
4-3 Analog Input/Output Module
4-3-2 Memory allocation in Software Set Range Operation mode
In Software Set Range Operation mode, memory allocation differs between when operating in A/D conversion mode (during
normal operation) and when operating in parameter mode.
<When operating in conversion mode>
When operating in conversion mode, memory allocation becomes as follows:
This module to CPU module
CPU module to this module
Offset
address
15(F)
+0
+1
+2
+3
+4
+5
+6
+7
Channel 1 Digital output value / Status
Channel 2 Digital output value / Status
Channel 3 Digital output value / Status
Channel 4 Digital output value / Status
Channel 5 Digital input value
Channel 6 Digital input value
Unused (fixed to 0 (zero))
Unused (fixed to 0 (zero))
0
<When operating in parameter mode>
Parameter mode is activated when bit 7 of the parameter type setting register is set ON. In parameter mode, memory
allocation becomes as follows:
This module to CPU module
CPU module to this module
Offset
address
15(F)
+0
+1
+2
+3
+4
+5
+6
+7
0
Status
Parameter type setting status
Parameter setting request
Parameter type setting
Parameter read data
Parameter setting data