2-17
Section 2 Specifications
I At shipment, both “Average” and “Range” switches are set to “0” (zero).
<Range switch setting list>
Switch N o.
NP1AXH8V-MR
Switch N o.
NP1AXH8I-MR
Input range
Digital output
range
Input range
Digital output
range
0
At shipment
-10 to 10 V -8000 to 8000 0
At shipment
4to20mA
0 to 16000
1 0 to 10 V 0 to 16000 1 0 to 20 mA
2 0 to 5 V 2 -20 to 20 mA -8000 to 8000
3 1to5V 3 4to20mA
0 to 100004 -10 to 10 V 0 to 10000 4 0 to 20 mA
5 0to10V 5 -20to20mA
6 0 to 5 V 6 Software S et Range Operation mode
7 1to5V 7
Unused (Note 2)
8 Software Set Range Operation mode (Note1) 8
9 Unused (Note 2) 9
<Average switch setting list>
Switch N o. NP1AXH8V-MR NP1AXH8I-MR
0
At shipment
Once (no moving average)
1Twice
24times
38times
4 to 9 Unused (no moving average)
Note 1:
For how to set in Software Set Range Operation mode,
refer to “Section 4 Software Interface”.
Note 2:
If an unused number is set, a “switch setting error” will
occur.
0
7
8
6
3
2
4
5
1
9
3
4
1
2
6
7
9
8
0
5
2) Operation setting switches
These switches are used to set input range and moving average execution times.
“Average” switch: Used to set a same value of moving average execution times for all channels. In Software Set Range
Operation mode, the setting of this switch is ignored, and instead the initial value is used for operation.
For more information, refer to “Section 4 Software Interface”.
“Range” switch: When this switch is set to one of numbers “0” to “7”, same range is set for all channels. It is impossible to
set input range differently for individual channels.
When this switch is set to “8”, Software Set Range Operation mode is activated, and it becomes possible
to set various parameters differently for individual channels. For more information, refer to “Section 4
Software Interface”.
3) Detachable terminal block
M3 20-pole detachable terminal block. For terminal arrangement, refer to “5-1-1 Terminal arrangement”. For wiring, be sure to
use crimp type terminals and surely tighten them (tightening torque: 0.5 to 0.7 N-m.)
4) Version seal
Versions of the hardware and firmware of the module are indicated on this seal.
2 0
3 0
Hardware version
Firmware version
2-5 Names and Functions