Loading...
2-19
Section 2 Specifications
(2) Functions
1) Status indication LED
Indicates the current status of the analog output module.
Symbol Color Descrip tion
ONL Green Lights when the module i s operating normally. Blinks
whileconnectingtoSXbus.
ERR Red Lights when the module i s abnormal.
SE TTING Green Blinks while gai n or offset value is being adjusted.
<Example of status indication>
O: Lighting, U: Blinking, -: Unlit
Status ONL (green) ERR (red) SETTIN G (green)
Initializing
U
--
Normally operating O - -
Adjusti ng offset/gain value O -
U
Fatal fault - O -
2) Operation setting switch
Used to set output range.
“Range” switch: When this switch is set to one of numbers “0” to “7” (“0” to “3” for current output modules), same output
range is set for all channels. It is impossible to set output range differently for individual channel.
When this switch is set to “8” (“4” for current output modules), Software Set Range Operation mode is
activated, and it becomes possible to set various parameters differently for individual channel. For more
information, refer to “Section 4 Software Interface”.
0
7
8
6
3
2
4
5
1
9
I At shipment, this switch is set to “0” (zero).
<Range switch setting list>
Switch N o.
NP1AYH8V-MR
Switch N o.
NP1AYH8I-MR
Output range
Digital input
range
Output range
Digital input
range
0
At shipment
0 to 10 V 0 to 16000 0
At shipment
4 to 20 mA 0 to 16000
1 0to5V 1 0to20mA
2 1 to 5 V 2 4 to 20 mA 0 to 10000
3 -10 to 10 V -8000 to 8000 3 0 to 20 mA
4 0 to 10 V 0 to 10000 4 Software Set Range Operation mode
5 0to5V 5
Unused (the operation for switch No. 0
)
6 1to5V 6
7 Unused (the operation for switch No. 0) 7
8 Software Set Range Operation mode (Note) 8
9 Unused (the operation for switch No. 0) 9
Note: For how to set in Software Set Range Operation mode, refer to "Section 4 Software Interface".
2-5 Names and Functions

Table of Contents

Related product manuals