Section 2 Specifications
2-22
2-5 Names and Functions
2) Operation setting switches
These switches are used to set input/output range. When input/output range is set with these switches, the same range is set
for input and output channels. It is impossible to set input range differently for individual channels.
0
7
8
6
3
2
4
5
1
9
3
4
1
2
6
7
9
8
0
5
Switch N o. Input range Digital output range Switch No. Output range D igital input range
0
At shipment
0to10V
0 to 16000
0
At shipment
0to10V
0 to 16000
1 0to5V 1 0to5V
2 1to5V 2 1to5V
3 -10 to 10 V -8000 to 8000 3 -10 to 10V -8000 to 8000
40to20mA
0 to 16000
40to20mA
0 to 16000
5 4 to 20 mA 5 4 to 20 mA
6 -20 to 20mA -8000 to 8000 6
Unused (the operation for switch No. 0)
7 Software Set Range Operation mode (Note) 7
8 Unused (the operation for switch No. 0) 8
9 Unused (the operation for switch No. 0) 9
Note: For how to set in Software Set Range Operation mode, refer to "Section 4 Software Interface".
3) Detachable terminal block
M3 20-pole detachable terminal block. For terminal arrangement, refer to “5-3-1 Terminal arrangement”. For wiring, be sure to
use crimp type terminals and surely tighten them (tightening torque: 0.5 to 0.7 N-m.)
4) Version seal
Versions of the hardware and firmware of the module are indicated on this seal.
2 0
3 0
Hardware version
Firmware version