App.1-2
Appendix 1 Offset/Gain Adjustment <D300win>
Appendix 1-1 Offset/Gain Adjustment of Analog Input Module
2) Offset is adjusted first.
Set ON bit 7 and bit 6 of the parameter type setting register (offset address +8) to activate offset/gain adjustment mode.
Bit 6 of the parameter type setting status register (offset address +1)
is set ON, indicating that offset/gain adjustment mode is activated.
Make sure that module
status is "30001".
3) Set ON the bit for the channel that is to be adjusted (the corresponding one of bits 8 to 15 of the parameter type setting
register). (The "SETTING" LED of the module starts blinking.)
Channel 8 Channel 7 Channel 6 Channel 5 Channel 4 Channel 3 Channel 2 Channel 1
The bit of the parameter type
setting status register that
corresponds to the channel to
be adjusted is set ON. In this
example, bit 8 (channel 1) is
set ON.