App.1-4
Appendix 1 Offset/Gain Adjustment <D300win>
Appendix 1-1 Offset/Gain Adjustment of Analog Input Module
6) When offset/gain adjustment mode is activated, offset adjustment value can be monitored.
Input the first channel number of the channels that are to be monitored to the parameter setting data register (offset
address +9), and the statuses of offset values for 5 channels will be displayed in the fields for offset addresses +3 to +7 of
the parameter read data register. (Gain adjustment values can be monitored in the same way.)
The statuses of offset values
can be monitored.
Set “1” (one) when you want
to monitor channel 1 (one)
and following channels.
7) Set ON bit 15 of the parameter type setting register and adjust gain.
Bit 15 of the parameter type setting
status register is set ON.