App.1-7
Appendix 1 Offset/Gain Adjustment <D300win>
Appendix 1-2 Offset/Gain Adjustment of Analog Output Module
<Offset/gain adjustment with SX Control Utility of D300win>
1) Start SX Control Utility to monitor the input/output areas of the analog output module that is to be adjusted.
Input/output status of
analog output module
(of 8ch specification)
2) Offset is adjusted first.
Input a value in the range from "30000" to "32767" to offset address +4 to change mode.
Make sure that bit 15 of the module status register
(offset address +0) is set ON (parameter mode).