9.2.11 ControlLogix Example: EDS Add-On Profile (AOP)
This section will demonstrate how to setup and use an EtherNet/IP I/O connection via EDS Add-On
Profile. This example only applies to RSLogix5000 V20 (and later) that support EDS Add-On Profile.
Otherwise, refer to the I/O examples in s ection 9.2.12. This section must be completed prior to
attempting any of the following AOP example(s).
EtherNet/IP I/O messaging allows the inverter’s function codes to be directly mapped into tags in the
ControlLogix PLC. Once an I/O connection is established, it is automatically synchronized at an interval
defined by the Requested Packet Interval (RPI).
1) Register the interface card’s EDS file. In the menu bar, navigate to ToolsEDS Hardware
Installation Tool. Refer to Figure 43.
Figure 43: EDS Hardware Installation Tool Menu
2) This will start the “EDS Wizard”. ClickNext”.
3) Select “Register an EDS file(s)” and click “Next”.
4) The “Registration dialog will appear. Refer to Figure 44.
Figure 44: EDS Registration
ClickBrowse”, select the interface cards EDS file, and clickNext.
5) Ensure that there are no errors in the test results. ClickNext.
6) A graphic image of the interface card is displayed. Click “Next”.