Inactive Text
Specifies the description of the obj ect’s “inactive” state. Enter a string of up to 32 characters in length.
This field is optional and may be left blank.
Relinquish Default
Defines the default value to be used for an object’s present value property when all entries in the
object’s priority array are NULL.
9.4.14 Multi-state Input Object Settings
Object Name
The name of the BACnet object. Enter a string of between 1 and 32 characters in length. All object
names must be unique within a node.
Instance
The BACnet object’s instance number. Enter a value between 0…4194302 (0x0…0x3FFFFE).
Function Code
The inverter function code (refer to section 4) that the BACnet object’s present value will access.
Data Type
Fixed at 16-Bit Unsigned.
9.4.15 Multi-state Output Object Settings
Object Name
The name of the BACnet object. Enter a string of between 1 and 32 characters in length. All object
names must be unique within a node.
Instance
The BACnet object’s instance number. Enter a value between 0…4194302 (0x0…0x3FFFFE).
Function Code
The inverter function code (refer to section 4) that the BACnet object’s present value will access.
Data Type
Fixed at 16-Bit Unsigned.
Relinquish Default
Defines the default value to be used for an object’s present value property when all entries in the
object’s priority array are NULL.
9.4.16 Multi-state Value Object Settings
Object Name
The name of the BACnet object. Enter a string of between 1 and 32 characters in length. All object
names must be unique within a node.
Instance
The BACnet object’s instance number. Enter a value between 0…4194302 (0x0…0x3FFFFE).
Function Code
The inverter function code (refer to section 4) that the BACnet object’s present value will access.
Data Type
Fixed at 16-Bit Unsigned.
Relinquish Default
Defines the default value to be used for an object’s present value property when all entries in the
object’s priority array are NULL.