9.4 BACnet/IP
• The interface card supports the BACnet/IP (Annex J) protocol over Ethernet via a configurable
UDP port (default value of 47808).
• The BACnet driver does not trigger timeout events (section 5.4.1
).
9.4.1 Protocol Implementation Conformance Statement
BACnet Protocol
Date: January 11, 2016
Vendor Name: ICC, Inc.
Product Name: Fuji FRENIC-Ace
Product Model Number: OPC-PRT
Applications Software Version: V1.1.31
Firmware Revision: V1.1.31
BACnet Protocol Revision: 2
Product Description:
The Fuji Electric FRENIC series is a family of high-performance multifunctional inverters.
Other features include ROHS compliance and built-in EMC filter.
BACnet Standard Device Profile (Annex L):
BACnet Operator Workstation (B-OW S)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specific Controller (B-ASC)
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)
BACnet Interoperability Building Blocks Supported (Annex K):
Data Sharing – ReadProperty-B (DS-RP-B)
Data Sharing – ReadPropertyMultiple-B (DS-RPM-B)
Data Sharing – W riteProperty-B (DS-WP-B)
Device Management – Dynamic Device Binding-B (DM-DDB-B)
Device Management – Dynamic Object Binding-B (DM-DOB-B)
Segmentation Capability:
None
Segmented requests supported Window Size ________
Segmented responses supported Window Size ________
Standard Object Types Supported:
See “Obj ect Types/Property Support Table”.
Data Link Layer Options:
BACnet IP, (Annex J)
BACnet IP, (Annex J), Foreign Device
ISO 8802-3, Ethernet (Clause 7)
ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s) ______
MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 76800
MS/TP slave (Clause 9), baud rate(s): ______
Point-To-Point, EIA 232 (Clause 10), baud rate(s): ______
Point-To-Point, modem, (Clause 10), baud rate(s): ______
LonTalk, (Clause 11), medium: ______
Other: ______