88
Device Address Binding:
Is static device binding supported? (This is currently for two-way communication with MS/TP slaves and
certain other devise.)
Yes No
Networking Options:
Router, Clause 6 - List all routing configurations
Annex H, BACnet Tunneling Router over IP
BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by Foreign Devices? Yes No
Character Sets Supported:
Indicating support for multiple character sets does not imply that they can all be supported
simultaneously.
ANSI X3.4 IBM™/Microsoft™ DBCS ISO 8859-1
ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS C 6226
If this product is a c ommunication gateway, describe the types of non-BACnet equipment/networks(s)
that the gateway supports: N/A
Datatypes Supported:
The following table summarizes the datatypes that are accepted (in the case of a write property service)
and returned (in the case of a read property service) when targeting the present value property of each
supported object type.
Object Type
Service
Read Property Write Property
Analog Output
Real
Real, Unsigned, Integer, Null
Analog Input
Real
N/A
Analog Value
Real
Real, Unsigned, Integer, Null
Binary Output
Enumerated
Enumerated, Boolean, Real, Unsigned, Integer, Null
Binary Input
Enumerated
N/A
Binary Value
Enumerated
Enumerated, Boolean, Real, Unsigned, Integer, Null
Multi-state Output
Unsigned
Enumerated, Real, Unsigned, Integer, Null
Multi-state Input
Unsigned
N/A
Multi-state Value
Unsigned
Enumerated, Real, Unsigned, Integer, Null
Notes:
The Null data type is used to relinquish a previously-commanded entry at the targeted priority in
the priority array.