94
9.4.9 Analog Output Object Settings
Object Name
The name of the BACnet object. Enter a string of between 1 and 32 characters in length. All object
names must be unique within a node.
Instance
The BACnet object’s instance number. Enter a value between 0…4194302 (0x0…0x3FFFFE).
Function Code
The inverter function code (refer to section 4) that the BACnet objects present value will access.
Data Type
Fixed to 16-bit Unsigned.
Units
Select the desired units from this dropdown menu. If the desired units are not available in the dropdown
menu, selectOther Units” and enter the appropriate enumerated value (as defined by the BACnet
Specification) in the “Unit Value” field.
Unit Value
This field is enabled only when the “Units” selection is set to “Other Units”. Enter the appropriate
enumerated value (as defined by the BACnet Spec ification.)
Relinquish Default
Defines the default value to be used for an object’s present value property when all entries in the
object’s priority array are NULL.
9.4.10 Analog Value Object Settings
Object Name
The name of the BACnet object. Enter a string of between 1 and 32 characters in length. All object
names must be unique within a node.
Instance
The BACnet object’s instance number. Enter a value between 0…4194302 (0x0…0x3FFFFE).
Function Code
The inverter function code (refer to section 4) that the BACnet objects present value will access.
Data Type
Fixed to 16-bit Unsigned.
Units
Select the des ired units from this dropdown menu. If the desired units are not available in the dropdown
menu, selectOther Units” and enter the appropriate enumerated value (as defined by the BACnet
Specification) in the “Unit Value” field.
Unit Value
This field is enabled only when the “Units” selection is set to “Other Units”. Enter the appropriate
enumerated value (as defined by the BACnet Spec ification.)
Relinquish Default
Defines the default value to be used for an object’s present value property when all entries in the
objects priority array are NULL.
9.4.11 Binary Input Object Settings
Object Name
The name of the BACnet object. Enter a string of between 1 and 32 characters in length. All object
names must be unique within a node.