Code
Name
Data setting range
Incr
e-
ment
Unit
Change
w
hen
running
Data
cop
ying
Default
setting
F02
Operation Method
0: RUN/STOP keys on keypad (Motor
rotational direction specified by terminal
command FWD/REV)
1: Terminal command FWD or REV
2: RUN/STOP keys on keypad (forward)
3: RUN/STOP keys on keypad (reverse)
N
Y
2
F03
Maximum Frequency 1 25.0 to 400.0 0.1
Hz
N Y
60.0
F04
Base Frequency 1
25.0 to 400.0
0.1
Hz
N
Y
60.0
F05
Rated Voltage at Base
Frequency 1
0: Output a voltage in proportion to input
voltage
80 to 240: Output an AVR-controlled
voltage (for 200 V class series)
160 to 500: Output an AVR-controlled
voltage (for 400 V class series)
1 V N Y2
0
F06
Maximum Output
Voltage 1
80 to 240: Output an AVR-controlled
voltage (for 200 V class series)
160 to 500: Output an AVR-controlled
voltage (for 400 V class series)
1 V N Y2
220
(380)
F07
Acceleration Time 1 0.01 to 3600
Note: Entering 0.00 cancels the acceleration
time, requiring external soft-start.
0.
01
s Y Y 6.00
F08
Deceleration Time 1 0.01 to 3600
Note: Entering 0.00 cancels the deceleration
time, requiring external soft-start.
0.
01
s Y Y 6.00
F09
Torque Boost 1
0.0 to 20.0
(percentage with respect to "F05: Rated
Voltage at Base Frequency 1")
Note: This setting takes effect when F37 = 0,
1, 3, or 4.
0.1
%
Y Y
See Table A.
F10
Electronic Thermal Ov
erload
Protection for Motor 1
(Motor characteristics)
(Overload detection level)
(Thermal time constant)
1: For a general-purpose motor with shaft-
driven cooling fan
2: For an inverter-driven motor with
separately powered cooling fan
Y Y 1
F11
0.00: Disable, 0.01 to 100.0
1 to 135% of the rated current (allowable
continuous drive current) of the motor
0.01
A
Y
Y1
Y2
See Table A.
F12
0.5 to 75.0
0.1
min
Y
Y
5.0
F14
Restart Mode after Momentar
Power Failure
(Mode selection)
0: Disable restart (Trip immediately)
1: Disable restart (Trip after a recovery from
power failure)
2: Trip after decelerate-to-stop *2
4: Enable restart (Restart at the frequency
at which the power failure occurred, for
general loads)
5: Enable restart (Restart at the starting
frequency)
Y
Y
1
F15
Frequency Limiter (High) (Low
0.0 to 400.0
0.1
Hz
Y
Y
70.0
F16
0.0 to 400.0
0.1
Hz
Y
Y
0.0
5-3