4. HEATING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature,
as shown in Figure 7.
On the other hand, if switched in [HIGH] [QU], the indoor motor will run at a constant airflow
of [HEAT] operation modes QU, LOW, MED, HIGH, as shown in Table 5.
5. COOL AIR PREVENTION CONTROL (Heating mode)
6. DRY OPERATION
Refer to the Figure 4.
During the dry mode operation, the fan speed setting can not be changed.
When the compressor operates, the maximum value of the indoor fan speed is set as shown in Figure 8,
based on the detected temperature by the indoor heat exchanger sensor on heating mode.
When the compressor does not operate, the indoor fan motor operates [S-Lo] mode.
( Fig.7 : Airflow change - over ( Heating : AUTO ) )
( Fig.8 : Cool Air Prevention Control )
< [Hi] setting > < The other of [Hi] setting >
Indoor heat exchanger
temperature
Indoor heat exchanger
temperature
42°C
30°C
34°C
Indoor heat exchanger
temperature
Indoor heat exchanger
temperature
Hi
Me+
Lo
Cool air
prevention
39°C
37°C
37°C
32°C
24°C
S-Lo
TR-Ts > - 1.5 °C
=
- 2.5 °C > TR-Ts
- 1.5 °C > TR-Ts > - 2.5 °C
=
TR-Ts > - 1 °C
=
- 2 °C > TR-Ts
- 1 °C > TR-Ts > - 2 °C
=
When the room
temperature rises
When the room
temperature drops
TR : Room temperature
Ts : Setting temperature
S-LOW mode
Indoor heat exchanger
temperature
Indoor heat exchanger
temperature
HIGH mode
Indoor heat exchanger
temperature
Indoor heat exchanger
temperature
(1) Fan mode : HIGH (2) Fan mode : MED, LOW, QUIET
5-1. For AB / AU Type
5-2. For AR Type
HIGH mode
MED mode
LOW mode
S-Lo
Lo (Qu)
Cool air
prevention
Setting
FAN mode
32°C
34°C
24°C
39°C
37°C
30°C
37°C
30°C
32°C
24°C
LOW mode
S-LOW mode
37°C
30°C
32°C
24°C
SETTING
FAN MODE
LOW mode