1-3. DRY OPERATION
The compressor rotation speed shall change according to the temperature,
set temperature, and room temperature variation which the room temperature sensor
of the indoor unit has detected as shown in the fig 3.
( Table 3 : Compressor rotation speed )
01-03
Operating speed
29rps
Room
temperature
Room
temperature
Ts+1.5 °C
Ts+0.5 °C
( Fig.3 : Compressor Control based on Room Temperature )
Ts : Setting temperature
Compressor
ON
OFF
Indoor fan
Dry air flow
S-Lo
OFF
( Fig.4 : Indoor Fan Control )
10 30 60 180 60 180 60 10 30 (sec)
Temperature zone
0rps
X zone
Y zone
[ AB*A30/36LBT : Dry air flow 650rpm, S-Lo 250rpm ]
[ AR*A30/36LBTU : Dry air flow 550rpm, S-Lo 350rpm ]
[ AU*A30/36LBLU : Dry air flow 430rpm, S-Lo 270rpm ]
X zone
Compressor ON
Y zone
Compressor OFF