En-13
Filter
indicator
action
13
00 Enable
○
Enable or disable the filter
indicator. Setting 02 is for use
with a central remote control.
01 Disable
02
Display
only on
central
remote
control
Horizon-
tal swing
airow
direction
24
00 Default
○
Adjust the horizontal swing airflow
direction.
(For horizontal swing equipped
models)
01 Left half
02 Right half
Cool air
tem-
perature
trigger
30
00 Default
○
Adjust the cool air trigger
temperature. To lower the trigger
temperature, use setting 01. To
raise the trigger temperature, use
setting 02.
01 Adjust (1)
02 Adjust (2)
Hot air
tem-
perature
trigger
31
00 Default
○
Adjust the hot air trigger
temperature. To lower the trigger
temperature by 6 degrees C, use
setting 01. To lower the trigger
temperature by 4 degrees C, use
setting 02. To raise the trigger
temperature, use setting 03.
01 Adjust (1)
02 Adjust (2)
03 Adjust (3)
Auto
restart
40
00 Enable
Enable or disable automatic
system restart after a power
outage.
01 Disable
○
External
control
46
00 Start/Stop
○
Allow an external controller to
start or stop the system, or to
perform an emergency shutdown.
* If an emergency shutdown is
performed from an external
controller, all refrigerant systems
will be disabled.
01
Emergency
stop
Error
report
target
47
00 All
○
Change the target for reporting
errors. Errors can either be
reported in all locations, or only
on the wired remote.
01
Display
only on
central
remote
control
8. TEST OPERATION
]1
8.1. Test operation using PCB (Outdoor
unit)
• RefertotheInstallationManualfortheoutdoorunitifthe
PCB for the outdoor unit is to be used for the test operation.
8.2. Test operation using remote controller
• RefertotheInstallationManualfortheremotecontrolunitto
perform the test operation using the remote control unit.
• Whentheairconditionerisbeingtestrun,theOPERATION
andTIMERindicatorlampsashslowlyatthesametime.
Fordetails,pleaserefertotheManualof“IRReceiverUnit”or
“WiredRemoteController”.
9. CHECK LIST
]1
Pay special attention to the check items below when
installing the indoor unit(s). After installation is complete, be
sure to check the following check items again.
Check items
If not performed
correctly
Check
box
Has the indoor unit
been installed correctly?
Vibration, noise,
indoor unit may drop
Has there been a
check for gas leaks
(refrigerant pipes)?
No cooling, No heating
Has heat insulation
work been completed?
Water leakage
Doeswaterdraineasily
from the indoor units?
Water leakage
Is the voltage of the
power source the same
as that indicated on the
label on the indoor unit?
No operation, heat
or burn damage
Are the wires and
pipes all connected
completely?
No operation, heat
or burn damage
Is the indoor unit
grounded?
Short circuit
Is the connection cable
thespeciedthickness?
No operation, heat
or burn damage
Are the inlets and outlets
free of any obstacles?
No cooling, No heating
After installation is
completed, has the
proper operation
and handling been
explainedtotheuser?