EasyManua.ls Logo

FULTON VSRT-60 - Page 101

FULTON VSRT-60
118 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
APPENDIX - A
Fulton Ltd
Capacities
(Applies to elevations up to
2,000 ft)
VSRT Model
VSRT-40
Rated Input at High Fire
kW
478
Minimum Input at Low Fire
kW
80
Rated Output
Boiler
HP
kg/hr
kW
40
626
392
Fuel
Requirements
(Pressure requirements at rated
input)
VSRT Model
VSRT-40
Fuel Usage at Rated Input
(Natural Gas)*
M
3
/hr
43
Fuel Usage at Rated Input
(Propane Gas)**
M
3
/hr
18.3
Min Gas Pressure (NG or
LPG)
mbar
19
Max Gas Pressure (NG or
LPG)
mbar
35
*m³/hr based on 40.1mJ/m³ Natural Gas (2016 Dukes Report)
**m³/hr based on 94mJ/m³ Propane
Electrical
Requirements
(Applies to <20ppm NO
x
standar
blower motor and control options
VSRT Model
VSRT-40
Electrical Supply*
volts
Ø
Hz
400
3
50
Control Voltage
Volts ac
110
IP Rating
54
Full Load Amps (FLA)
Amps
21.6
d
)
*Includes Burner fan motor, feedwater pump & standard control circuit.
Weights &
Water Volume
VSRT Model
VSRT-40
Dry Weight
kg
2,654
Operating Weight at
Normal Working Level
kg
3,959
Flooded Weight
kg
4,228
Water Volume at Normal
Working Level
Litres
1,306
VSRT-IOMM-2019-1