8.1 TROUBLESHOOTING GAS BOILER
Check for gas pressure and intermittent supply problems.
Check fuse or circuit breaker.
Reset or Replace as required.
Check for cracks in porcelain, if found replace
the electrode. Check electrodes for carbon build-
up. Clean as required.
Check settings, adjust if required.
Check voltage between transformer leads at terminal block
to be sure transformer is live.
Check for ignition interference.
Check voltage between ignition terminal and neutral, this
check must be made before the control locks out. If no
power, replace the control.
Check air servo motor operation and setting.
Check for faulty air switch.
Check filters in the valve block. Clean as required.
10. Loose wire connections
Check connections to all components.
2. Flame Failure During
Start-up
Check for gas pressure and intermittent supply problems.
Check fuse or circuit breaker.
Reset or Replace as required.
Check air servo motor operation and setting.
Check for cracks in porcelain, if found replace
the electrode. Check electrodes for carbon build-
up. Clean as required.
Check settings, adjust if required.
Check the detector is located correctly and clean.
Check voltage between ignition terminal and neutral, this
check must be made before the control locks out. If no
power, replace the control.
7. Loose wire at fuel valve circuit.
Tighten wiring connections.
8. Contact open on Air Switch
Adjust to the correct setting.
9. UV Detector wiring reversed at
control box.
Change to the correct terminals.