8.1 TROUBLESHOOTING GAS BOILER
Check air and gas servo motors and check CO2 and O2
combustion levels.
Check draft with a gauge. Draft should be -.05 to -.10 mbar
with the burner off, or -.10 to -.15 mbar when operating.
A barometric damper may need to be installed.
Check draft complies with min/max parameters
(Technical Data Sheet Appendix A).
4. Negative Room Pressure
Ensure there are no exhaust fans running in the boiler
room.
Check fan for obstructions, clean as required.
Check for cracks in porcelain, if found replace
the electrode. Check electrodes for carbon build-
up. Clean as required.
Check settings, adjust if required.
Check the detector is located correctly and clean.
Check draft complies with min/max parameters (Technical
Data Sheet Appendix A).
4. Negative room pressure
Ensure no exhaust fans are running in the boiler room.
Check Air servo motor operation and setting.
Check gas pressure coming into the gas train, if low
contact the gas supplier.
Check the setting on the gas valve regulator, adjust as
required.
Check flue Carbon build up and or obstruction.