2. WIRING
2-17
2.2.3 MC-3000S Jumper and MODBUS settings
Set the jumper blocks in the MC-CS Board (24P0114) referring to the tables that
follow.
MC-CS Board (24P0114)
Setting MODBUS addresses: Use the rotary switch (S2) to set the Modbus address
when setting connectors J4/J5 to Modbus. The Modbus address set at J4/J5 in the
network is not used. When setting J4/J5 to IEC61162-1/2, use the default setting (“0”).
Setting termination resistors on the Jumper block:
Use the jumper block J19 to set the termination resistor on/off for the MODBUS
communication on the connector J1. For the first and last sensor adapter in a series,
their termination resistors should be set to ON. Use the MC-CS Board with the default
setting because it becomes the “first” adapter in a series.
Set the jumper blocks J14 through J17 to turn the termination resistors on connectors
J4 through J7 respectively.
(Termination resistor ON)
• When setting the starting/ending terminal for the multipoint, or the multipoint is not
connected (CH1 to 4).
• When setting the starting/ending terminal for Modbus (CH1, CH2)
Jumper block J19 Connector J1
1-2 SHORT Termination resistor: ON (default setting)
2-3 OPEN
1-2 OPEN Termination resistor: OFF
2-3 SHORT
S2
J14
J22 J23 J15 J16 J17
J19 J20 J21