Loading...
68K System Monitor
User's Guide
GE Energy Services
General SWM0023-1.00 -2
Full Release
3-19
D - Dump Memory
Platform
þ
CPM
þ
D20
D20 Base
þ
D20 ME
D20 Base
þ
D20/200
CCU Base
þ
D20/200 ME
CCU Base
þ
D25
Description
Use this command to display memory contents as bytes, words, long words, floating-
point numbers, or double-precision numbers.
Each line of output is formatted as:
at the left margin:
starting address of the memory, hexadecimal.
then:
16 bytes (octets) of data grouped as:
bytes hexadecimal format
words hexadecimal format
long words hexadecimal format
floating-point numbers scientific format
double-precision numbers scientific format
then:
16 ASCII characters representing the same memory values.
If an octet does not have a printable ASCII representation, the monitor will print a
dot instead.
Syntax
Below is usage and syntax information for this command
Command Format
d [/(b | w | l | f | d)] beg_addr [end_addr]
Variables
/b = bytes (octets), the default mode
/w = words
/l = long words
/f = floating-point numbers
/d = double-precision numbers
Parameters
By not entering any parameters, the command requests a dump
from the last user-entered memory dump location. The dump is
in the previously specified format (if any) and dumps for 80
bytes.
beg_addr = first address to display, in hexadecimal.
end_addr = address up to which to display, in hexadecimal;
the default is beg_addr plus 80 hexadecimal.
Continued on next page