CB Watch 3 User Manual v6.3 - May 2019 Page 24 of 100
Figure 31 Separation and touching speed
All speeds are expressed in meters per second (m/s)
Timing alarms
Alarm thresholds can be set for the following measured items:
Opening
Minimum and maximum Reaction time (t1), per pole
Maximum t1 pole to pole discrepancy
Minimum and maximum Operation time (t2), per pole
Maximum t2 pole to pole discrepancy
Minimum and maximum Travel time (t2-t1), per pole
Maximum t2-t1 pole to pole discrepancy
Minimum contact separation speed, per pole
Closing
Minimum and maximum Reaction time (t1), per pole
Maximum t1 pole to pole discrepancy
Minimum and maximum Operation time (t2), per pole
Maximum t2 pole to pole discrepancy
Minimum and maximum Travel time (t2-t1), per pole
Maximum t2-t1 pole to pole discrepancy
The threshold values can be entered during setup here:
HMI: Settings/Opening and Settings/Closing
Figure 32 Operation timing alarms thresholds