EasyManua.ls Logo

GE CB Watch 3 - Extrapolated Gas Pressure Alarms; Gas Measurement History Graphs

GE CB Watch 3
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CB Watch 3 User Manual v6.3 - May 2019 Page 44 of 100
If not enough data is available to fill the short term or long term horizon set, then the
value cannot be calculated and a “-“ is displayed instead.
HMI: Measurements/Gas
Figure 61 Gas leak rates (ganged CB)
Figure 62 Gas leak rates (IPO CB)
Gas alarms
Two alarms can be set on the extrapolated gas pressure values calculated. They rely on
the thresholds set in section 5.2.2 above:
The long-term alarm is raised if the extrapolated gas pressure at 20
o
C is
calculated to drop below the gas threshold 1 (nearly too low) that has been set
This means that the gas pressure/level will be below threshold 1 within the
long-term horizon that has been set
The short-term alarm is raised if the extrapolated gas pressure at 20
o
C is
calculated to drop below the gas threshold 2 (too low, lock-out) that has been set
This means that the gas pressure/level will be below threshold 2 within the
short-term horizon that has been set
HMI: Measurements/Alarms
Figure 63 Gas alarms
Gas measurement history
On the HMI, you can view graphs displaying the history of the key gas parameters. Using
the drop down menu, you can select either:
Short term graphs: with resolution of 1 value every 10 minutes
Long term graphs: with resolution of 1 value per day

Table of Contents

Related product manuals