CB Watch 3 User Manual v6.3 - May 2019 Page 29 of 100
Overtravel
The overtravel is also monitored for each operation. This is defined as the difference (in
mm) between these two measured values:
- The maximum travel point reached during the operation
- The final resting position at the end of the operation
as measured by the travel sensor and shown on the travel curve
Figure 39 Monitoring the overtravel
HMI: Measurements/Last opening results and Last closing results
Figure 40 Displaying overtravel
An alarm threshold can be entered for the maximum overtravel: