7-42 F650 Digital Bay Controller GEK-106310AB
7.2 IEC 61850 PROFILE FOR F650 7 IEC 61850 PROTOCOL
7
2.5.1.4 geRemoteInputsGGIO
This logical node class is used is used to map data from incomming GOOSE messages.
2.5.1.5 geRemoteOutputsGGIO
This logical node class is used is used to map PLC digital states for outgoing GOOSE messages.
Note: In 650 relays data from all logical nodes can be sent through outgoing GOOSE messages. Apart from that, logical
node rouGGIO gives the ability to send through GOOSE digital states that are results of PLC logic equotions. Mapping and
configuraion of rouGGIO states should be done with Enervista650 software.
GGIO class
Attribute
Name
Attribute
Type
Explanation M/O/E Notes
GGIO Generic process I/O
Data
Common Logical Node Information
Mod INC Mode M Status-only
Beh INS Behaviour M
Health INS Health M
NamPlt LPL Name plate M
Status information
Ind1 SPS General Indication ( binary
input )
O Remote Digital Input 1
Ind2 SPS General Indication ( binary
input )
O Remote Digital Input 2
......... .......... ............... .......... ..............
Ind32 SPS General Indication ( binary
input )
O Remote Digital Input 32
AnIn1 SPS Analogue input O Remote Analogue Input 1
AnIn2 SPS Analogue input O Remote Analogue Input 2
......... .......... ............... .......... ..............
AnIn16 SPS Analogue input O Remote Analogue Input 16
GGIO class
Attribute
Name
Attribute
Type
Explanation M/O/E Notes
GGIO Generic process I/O
Data
Common Logical Node Information
Mod INC Mode M Status-only
Beh INS Behaviour M
Health INS Health M
NamPlt LPL Name plate M
Status information
Ind1 SPS General Indication ( binary
input )
O Remote Digital Output 1
Ind2 SPS General Indication ( binary
input )
O Remote Digital Output 2
......... .......... ............... .......... ..............
Ind31 SPS General Indication ( binary
input )
O Remote Digital Output 31
Ind32 SPS General Indication ( binary
input )
O Remote Digital Output 32