GEK-106310AB F650 Digital Bay Controller B-107
APPENDIX B B.7 MEMORY MAP
B
Ajustes DNP 3.0 Esclavo 3 - DNP 3.0 Slave 3(cont.)
8=CTL EVENTS 113-128
9=SWITCHGEAR 1-8
10=SWITCHGEAR 9-16
0x2DE0 Confirmation address W 1
Ajustes Unidad Sobreintensidad Instantánea de Tierra Aislada Grupo 1 - Isolated Ground IOC 1 Settings
0x2DF6 Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x2DF7 Vh Level F003 1 R/W 2 [2 , 70] V
0x2DF9 Il LEVEL F003 1 R/W 2 [0.005 , 0.400] A
0x2DFB Vl LEVEL F003 1 R/W 2 [2 , 70] V
0x2DFD Ih LEVEL F003 1 R/W 2 [0.005 , 0.400] A
0x2DFF Delay F003 1 R/W 2 [0.00 , 900.00] s
0x2E01 Time to inst F003 1 R/W 2 [0.00 , 900.00] s
0x2E03 Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x2E16 Confirmation address W 1
Ajustes Unidad Sobreintensidad Instantánea de Tierra Aislada Grupo 2 - Isolated Ground IOC 2 Settings
0x2E17 Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x2E18 Vh Level F003 1 R/W 2 [2 , 70] V
0x2E1A Il LEVEL F003 1 R/W 2 [0.005 , 0.400] A
0x2E1C Vl LEVEL F003 1 R/W 2 [2 , 70] V
0x2E1E Ih LEVEL F003 1 R/W 2 [0.005 , 0.400] A
0x2E20 Delay F003 1 R/W 2 [0.00 , 900.00] s
0x2E22 Time to inst F003 1 R/W 2 [0.00 , 900.00] s
0x2E24 Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x2E37 Confirmation address W 1
Ajustes Unidad Sobreintensidad Instantánea de Tierra Aislada Grupo 3 - Isolated Ground IOC 3 Settings
0x2E38 Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x2E39 Vh Level F003 1 R/W 2 [2 , 70] V
0x2E3B Il LEVEL F003 1 R/W 2 [0.005 , 0.400] A
0x2E3D Vl LEVEL F003 1 R/W 2 [2 , 70] V
0x2E3F Ih LEVEL F003 1 R/W 2 [0.005 , 0.400] A
0x2E41 Delay F003 1 R/W 2 [0.00 , 900.00] s
0x2E43 Time to inst F003 1 R/W 2 [0.00 , 900.00] s
0x2E45 Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x2E58 Confirmation address W 1
Ajustes Unidad Direccional de Tierra Sensible Grupo 1 - Sensitive Ground Directional 1 Settings
0x2E59 Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x2E5A MTA F003 1 R/W 2 [-90 , 90] Deg
0x2E5C Direction F012 1 R/W 1 0=REVERSE
1=FORWARD
ADDRESS BIT NAME FORMAT STEP MODE LENGTH MISCELLANEOUS