B-108 F650 Digital Bay Controller GEK-106310AB
B.7 MEMORY MAP APPENDIX B
B
Ajustes Unidad Direccional de Tierra Sensible Grupo 1 - Sensitive Ground Directional 1 Settings(cont.)
0x2E5D Block Logic F012 1 R/W 1 0=PERMISSION
1=BLOCK
0x2E5E Pol V Threshold F003 1 R/W 2 [0 , 300] V
0x2E60 Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x2E73 Confirmation address W 1
Ajustes Unidad Direccional de Tierra Sensible Grupo 2 - Sensitive Ground Directional 2 Settings
0x2E74 Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x2E75 MTA F003 1 R/W 2 [-90 , 90] Deg
0x2E77 Direction F012 1 R/W 1 0=REVERSE
1=FORWARD
0x2E78 Block Logic F012 1 R/W 1 0=PERMISSION
1=BLOCK
0x2E79 Pol V Threshold F003 1 R/W 2 [0 , 300] V
0x2E7B Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x2E8E Confirmation address W 1
Ajustes Unidad Direccional de Tierra Sensible Grupo 3 - Sensitive Ground Directional 3 Settings
0x2E8F Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x2E90 MTA F003 1 R/W 2 [-90 , 90] Deg
0x2E92 Direction F012 1 R/W 1 0=REVERSE
1=FORWARD
0x2E93 Block Logic F012 1 R/W 1 0=PERMISSION
1=BLOCK
0x2E94 Pol V Threshold F003 1 R/W 2 [0 , 300] V
0x2E96 Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x2EA9 Confirmation address W 1
Ajustes Unidad de Potencia Máxima Directa Grupo 1 - Forward Power 1 Settings
0x2EAA Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x2EAB Blk Time After Close F003 1 R/W 2 [0.00 , 900.00] s
0x2EAD Stage 1 Tap F003 1 R/W 2 [0.00 , 10000.00] MW
0x2EAF Stage 1 Time F003 1 R/W 2 [0.00 , 900.00] s
0x2EB1 Stage 2 Tap F003 1 R/W 2 [0.00 , 10000.00] MW
0x2EB3 Stage 2 Time F003 1 R/W 2 [0.00 , 900.00] s
0x2EB5 Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x2EC8 Confirmation address W 1