6.3.4 POR AIDED TRIPPING LOGIC
V03513
Aided 1 Receive
Aid. 1 Selection
POR
&
Aid1 Trip Enable
&
Send on Trip
None
Any Trip
Trip Inputs 3Ph
&
&
1
t
RGD
tReversal Guard
Blk Send
Any Trip
Any Trip
&
Send on Trip
Aided / Z1
Aid 1 Distance
Disabled
&
1 100ms
&
1
Echo Send
&
1
Aided 1 Receive
Aid. 1 Selection
POR
&
Blk Send
VTS Slow Block
&
250 ms
CB Open 3 ph
1
10 ms
100 ms
CB Open A ph
CB Open B ph
CB Open C ph
1
&
Weak Infeed
Echo
Echo and Trip
Signal Send
Zone 1 Trip
Aid 1 Dist Trip
Aid 1 DEF Trip
100 ms
R
Q
S
&
&
60 ms
Week Infeed
Snapshot Logic
Aided 1 WI V < A
Aid 1 WI Trip A
Aid 1 WI Trip B
Aid 1 WI Trip C
Aided 1 WI V < B
Aided 1 WI V < C
WI Sngl Pole Trp
Disabled
Aid1 WI Trip 3Ph
&
1
1
Any Zone 4 element
DEF reverse element
1Delta reverse element &
Distance signal send
Delta signal send
DEF signal send 1
Figure 129: POR Aided Tripping logic
P543i/P545i Chapter 8 - Carrier Aided Schemes
P54x1i-TM-EN-1 243

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE MiCOM P40 Agile and is the answer not in the manual?

GE MiCOM P40 Agile Specifications

General IconGeneral
BrandGE
ModelMiCOM P40 Agile
CategoryControl Unit
LanguageEnglish

Related product manuals