EasyManuals Logo

GE MiCOM P40 Agile User Manual

GE MiCOM P40 Agile
802 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #314 background imageLoading...
Page #314 background image
V02775
jX
-jX
R-R
-10°
20%
Power Swing region
(shaded area)
Blind Region
Zone x
Operate Region
Blind Region
Load blinder boundary
Figure 153: Load Blinder Boundary Conditions
The area is defined by lines created with angles fixed at 10° closer to the resistive axis than those created by the
load blinder angle setting (Load/B Angle - 10°) and a circular arc with a radius concentric with, and equivalent
to 20% greater than, the load blinder impedance setting (Z< Blinder Imp + 20%).
This is clearly indicated with reference to the diagram.
Note:
This power swing conditions are completely independent of the slow swing associated with Zone 7 and Zone 8.
3.5
POWER SWING BLOCKING LOGIC
The Power Swing function follows the logic diagram below:
Chapter 10 - Power Swing Functions P543i/P545i
278 P54x1i-TM-EN-1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE MiCOM P40 Agile and is the answer not in the manual?

GE MiCOM P40 Agile Specifications

General IconGeneral
BrandGE
ModelMiCOM P40 Agile
CategoryControl Unit
LanguageEnglish

Related product manuals