5.11.2 1-PHASE DEAD TIME LOGIC DIAGRAM
V03342
CB1LSPAR 1P DTime&
&
Seq Counter = 1
CB1LSPAR
DTOK CB 1P
DTOK All
&
&
R
Q
S
& OKTimeSP
DT Start by Prot
Protection Reset
&
AR Start
1
CB1LSPAR
CB1OP2/ 3P
0
t
CB1LSPAR
&
Logic 1
1
1 Pole Dead Time
CB1SPDTCOMP
Figure 189: Single-phase Dead Time logic diagram (Module 24)
P543i/P545i Chapter 11 - Autoreclose
P54x1i-TM-EN-1 331