EasyManua.ls Logo

GE MiCOM P40 Agile - Figure 189: Single-Phase Dead Time Logic Diagram (Module 24)

GE MiCOM P40 Agile
802 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.11.2 1-PHASE DEAD TIME LOGIC DIAGRAM
V03342
CB1LSPAR 1P DTime&
&
Seq Counter = 1
CB1LSPAR
DTOK CB 1P
DTOK All
&
&
R
Q
S
& OKTimeSP
DT Start by Prot
Protection Reset
&
AR Start
1
CB1LSPAR
CB1OP2/ 3P
0
t
CB1LSPAR
&
Logic 1
1
1 Pole Dead Time
CB1SPDTCOMP
Figure 189: Single-phase Dead Time logic diagram (Module 24)
P543i/P545i Chapter 11 - Autoreclose
P54x1i-TM-EN-1 331

Table of Contents

Related product manuals