2 RECOMMENDED CT CLASSES
You can use Class X current transformers with a knee point voltage greater or equal to that calculated. You can
also use class 5P protection CT. These have a knee-point voltage equivalent, which can be approximated from the
following calculations:
V
k
= (VA
´
ALF)/I
n
+ (R
CT
´
ALF
´
I
n
)
where:
V
k
= Knee-point voltage
VA = Voltampere burden rating
ALF = Accuracy limit factor
I
n
= CT nominal secondary current
R
CT
= CT resistance
Chapter 16 - Current Transformer Requirements P543i/P545i