4 CYBER-SECURITY IMPLEMENTATION
The General Electric IEDs have always been and will continue to be equipped with state-of-the-art security
measures. Due to the ever-evolving communication technology and new threats to security, this requirement is
not static. Hardware and software security measures are continuously being developed and implemented to
mitigate the associated threats and risks.
This section describes the current implementation of cyber-security. This is valid for the release of platform
software to which this manual pertains. This current cyber-security implementation is known as Cyber-security
Phase 1.
At the IED level, these cyber-security measures have been implemented:
NERC-compliant default display
Four-level access
Enhanced password security
Password recovery procedure
Disabling of unused physical and logical ports
Inactivity timer
Security events management
External to the IEDs, the following cyber-security measures have been implemented:
Antivirus
Security patch management
4.1
NERC-COMPLIANT DISPLAY
For the device to be NERC-compliant, it must provide the option for a NERC-compliant default display. The default
display that is implemented in our cyber-security concept contains a warning that the IED can be accessed by
authorised users. You can change this if required with the User Banner setting in the SECURITY CONFIG column.
ACCESS ONLY FOR
AUTHORISED USERS
HOTKEY
If you try to change the default display from the NERC-compliant one, a further warning is displayed:
DISPLAY NOT NERC
COMPLIANT OK?
The default display navigation map shows how NERC-compliance is achieved with the product's default display
concept.
P543i/P545i Chapter 23 - Cyber-Security
P54x1i-TM-EN-1 609

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE MiCOM P40 Agile and is the answer not in the manual?

GE MiCOM P40 Agile Specifications

General IconGeneral
BrandGE
ModelMiCOM P40 Agile
CategoryControl Unit
LanguageEnglish

Related product manuals