6-28 MM2 Motor Manager 2
GE Power Management
6.5 MEMORY MAP 6 COMMUNICATIONS
6
LOAD
PROTEC-
TION
con’t
44188 4187 105B Stalled Rotor Trip Level 115-455 5 0.01FLC F1* 450=4.50xFLC
44189 4188 105C Stalled Rotor Trip Delay 5-50 5 0.1 x s F1 30 = 3.0 s
44190 4189 105D ...Reserved... ... ... ... ... ...
44191 4190 105E ...Reserved... ... ... ... ... ...
44192 4191 105F ...Reserved... ... ... ... ... ...
CONFIG.
INPUTS
44193 4192 1060 Interlock Input 1 Function 0-34 1 --- F17 0 = NOT USED
44194 4193 1061 Startup Override Delay 0-3601 1 s F1* 0
44195 4194 1062 Running Override Delay 0-3601 1 s F1* 0
44196 4195 1063 Operation 0-1 1 --- F18 0 = IL STOP
44197 4196 1064 Instantaneous Alarm 0-1 1 --- F14 0 = DISABLE
44198 4197 1065 ...Reserved... ... ... ... ... ...
44199 4198 1066 ...Reserved... ... ... ... ... ...
44200 4199 1067 ...Reserved... ... ... ... ... ...
44201 4200 1068 Interlock Input 2 Function 0-34 1 --- F17 0 = NOT USED
44202 4201 1069 Startup Override Delay 0-3601 1 s F1* 0
44203 4202 106A Running Override Delay 0-3601 1 s F1* 0
44204 4203 106B Operation 0-1 1 --- F18 0 = IL STOP
44205 4204 106C Instantaneous Alarm 0-1 1 --- F14 0 = DISABLE
44206 4205 106D ...Reserved... ... ... ... ... ...
44207 4206 106E ...Reserved... ... ... ... ... ...
44208 4207 106F ...Reserved... ... ... ... ... ...
44209 4208 1070 Interlock Input 3 Function 0-34 1 --- F17 0 = NOT USED
44210 4209 1071 Startup Override Delay 0-3601 1 s F1* 0
44211 4210 1072 Running Override Delay 0-3601 1 s F1* 0
44212 4211 1073 Operation 0-1 1 --- F18 0 = IL STOP
44213 4212 1074 Instantaneous Alarm 0-1 1 --- F14 0 = DISABLE
44214 4213 1075 ...Reserved... ... ... ... ... ...
44215 4214 1076 ...Reserved... ... ... ... ... ...
44216 4215 1077 ...Reserved... ... ... ... ... ...
44217 4216 1078 Interlock Input 4 Function 0-34 1 --- F17 0 = NOT USED
44218 4217 1079 Startup Override Delay 0-3601 1 s F1* 0
44219 4218 107A Running Override Delay 0-3601 1 s F1* 0
44220 4219 107B Operation 0-1 1 --- F18 0 = IL STOP
44221 4220 107C Instantaneous Alarm 0-1 1 --- F14 0 = DISABLE
44222 4221 107D ...Reserved... ... ... ... ... ...
Table 6–12: MODBUS MEMORY MAP (Sheet 9 of 21)
GROUP MOD-
ICON
REGISTER
ADDRESS DESCRIPTION REGISTE
R VALUE
RANGE
STEP
VALUE
UNITS
AND
SCALE
FOR-
MAT
FACTORY
DEFAULT
VALUE
(CONVERTED)
DEC HEX
Notes: * – Maximum setpoint value and 65535 represent OFF
** – 1/Phase Current Scale Factor x A
*** – 101 represents unlimited
† – Minimum setpoint value represents OFF
~* – 0.1 x A when Hi resolution mode is disabled; 0.01 x A when enabled