GE Power Management
MM2 Motor Manager 2 6-27
6 COMMUNICATIONS 6.5 MEMORY MAP
6
MOTOR
PROTEC-
TION
THERMAL
44153 4152 1038 Full Load Current 0-1000 1 ** F1
†
0 = OFF
44154 4153 1039 High Speed Full Load Current 5-1000 1 ** F1 100
44155 4154 103A Overload Curve Number 1-12 1 --- F1 4
44156 4155 103B Hot / Cold Curve Ratio 20-100 1 % F1 75
44157 4156 103C Overload Pickup Level 100-125 1 0.01FLC F1 100=1.00xFLC
44158 4157 103D ...Reserved... ... ... ... ... ...
44159 4158 103E ...Reserved... ... ... ... ... ...
44160 4159 103F ...Reserved... ... ... ... ... ...
MOTOR
PROTEC-
TION
GROUND
44161 4160 1040 Ground Fault Alarm Level (5 A CT) 3-101 1 % CT F1* 65535 = OFF
44162 4161 1041 Gnd Fault Alarm Level (50:0.025 CT) 1-151 1 0.1 x A F1* 65535 = OFF
44163 4162 1042 Ground Fault Alarm Delay on Run 1-60 1 s F1 10
44164 4163 1043 Ground Fault Trip Level (residual) 3-101 1 % CT F1* 65535 = OFF
44165 4164 1044 Gnd Fault Trip Level (50:0.025 CT) 0-151 1 0.1 x A F1* 65535 = OFF
44166 4165 1045 Ground Fault Trip Delay on Run 0-100 1 0.1 x s F1 10 = 1.0
44167 4166 1046 Delay Contactor GF Trip By (Aux1) 0-1000 100 ms F1 0
44168 4167 1047 Delay Contactor GF Trip By (Aux2) 0-1000 100 ms F1 0
44169 4168 1048 ...Reserved... ... ... ... ... ...
MOTOR
PROTECTI
ON
OPTIONS
44170 4169 1049 Minimize Reset Time 0-1 1 --- F14 1 = ENABLE
44171 4170 104A Stopped Motor Cooling Time 5-1080 1 minutes F1 30
44172 4171 104B Overload Trip Reset 0-1 1 --- F16 0 = MANUAL
44173 4172 104C Phase Unbalance Alarm 0-1 1 --- F14 1 = ENABLE
44174 4173 104D Thermal Capacity Alarm 1-101 1 % F1* 101 = OFF
44175 4174 104E Open Control Circuit Trip 0-1 1 --- F14 0 = Disable
44176 4175 104F Reset Alarms using the Reset Key 0-1 1 --- F14 0 = Disable
LOAD
PROTEC-
TION
44177 4176 1050 Under Power Alarm Level 2-11001 1 0.1 xkW F1* 65535 = OFF
44178 4177 1051 Under Power Alarm Delay 1-60 1 s F1 10
44179 4178 1052 Under Power Trip Level 2-11001 1 0.1 xkW F1* 65535 = OFF
44180 4179 1053 Under Power Trip Delay 1-60 1 s F1 10
44181 4180 1054 Acceleration Time Alarm Delay 5-1255 5 0.1 x s F1* 65535 = OFF
44182 4181 1055 Acceleration Time Trip Delay 5-1255 5 0.1 x s F1* 65535 = OFF
44183 4182 1056 Load Increase Alarm Level 20-111 1 % FLC F1* 65535 = OFF
44184 4183 1057 Undercurrent Alarm Level 10-101 1 % FLC F1* 65535 = OFF
44185 4184 1058 Undercurrent Alarm Delay 1-60 1 s F1 10
44186 4185 1059 Undercurrent Trip Level 10-101 1 % FLC F1* 65535 = OFF
44187 4186 105A Undercurrent Trip Delay 1-60 1 s F1 10
Table 6–12: MODBUS MEMORY MAP (Sheet 8 of 21)
GROUP MOD-
ICON
REGISTER
ADDRESS DESCRIPTION REGISTE
R VALUE
RANGE
STEP
VALUE
UNITS
AND
SCALE
FOR-
MAT
FACTORY
DEFAULT
VALUE
(CONVERTED)
DEC HEX
Notes: * – Maximum setpoint value and 65535 represent OFF
** – 1/Phase Current Scale Factor x A
*** – 101 represents unlimited
† – Minimum setpoint value represents OFF
~* – 0.1 x A when Hi resolution mode is disabled; 0.01 x A when enabled