CHAPTER 1: THREE-PHASE POWER MEASUREMENT BLONDEL’S THEOREM AND THREE PHASE MEASUREMENT
EPM 2200 POWER METER – INSTRUCTION MANUAL 1–5
The theorem may be stated more simply, in modern language:
In a system of N conductors, N-1 meter elements will measure the power or energy 
taken provided that all the potential coils have a common tie to the conductor in 
which there is no current coil.
Three-phase power measurement is accomplished by measuring the three individual 
phases and adding them together to obtain the total three phase value. In older 
analog meters, this measurement was accomplished using up to three separate 
elements. Each element combined the single-phase voltage and current to produce a 
torque on the meter disk. All three elements were arranged around the disk so that the 
disk was subjected to the combined torque of the three elements. As a result the disk 
would turn at a higher speed and register power supplied by each of the three wires. 
According to Blondel's Theorem, it was possible to reduce the number of elements 
under certain conditions. For example, a three-phase, three-wire delta system could 
be correctly measured with two elements (two potential coils and two current coils) if 
the potential coils were connected between the three phases with one phase in 
common. 
In a three-phase, four-wire wye system it is necessary to use three elements. Three 
voltage coils are connected between the three phases and the common neutral 
conductor. A current coil is required in each of the three phases.
In modern digital meters, Blondel's Theorem is still applied to obtain proper      
metering. The difference in modern meters is that the digital meter measures each 
phase voltage and current and calculates the single-phase power for each phase. The 
meter then sums the three phase powers to a single three-phase reading.
Some digital meters measure the individual phase power values one phase at a time. 
This means the meter samples the voltage and current on one phase and calculates a 
power value. Then it samples the second phase and calculates the power for the 
second phase. Finally, it samples the third phase and calculates that phase power. 
After sampling all three phases, the meter adds the three readings to create the 
equivalent three-phase power value. Using mathematical averaging techniques, this 
method can derive a quite accurate measurement of three-phase power.
More advanced meters actually sample all three phases of voltage and current   
simultaneously and calculate the individual phase and three-phase power values. The 
advantage of simultaneous sampling is the reduction of error introduced due to the 
difference in time when the samples were taken.