1–4 EPM 2200 POWER METER – INSTRUCTION MANUAL
BLONDEL’S THEOREM AND THREE PHASE MEASUREMENT CHAPTER 1: THREE-PHASE POWER MEASUREMENT
Figure 1-4: Phasor Diagram, Three-Phase Voltages and Currents, Delta-Connected
Another common delta connection is the four-wire, grounded delta used for lighting 
loads. In this connection the center point of one winding is grounded. On a 120/240 
volt, four-wire, grounded delta service the phase-to-ground voltage would be 120 
volts on two phases and 208 volts on the third phase. Figure 1.5 shows the phasor 
diagram for the voltages in a three-phase, four-wire delta system.
Figure 1-5: Phasor Diagram Showing Three-phase Four-Wire Delta-Connected System
1.4 Blondel’s Theorem and Three Phase Measurement
In 1893 an engineer and mathematician named Andre E. Blondel set forth the first 
scientific basis for polyphase metering. His theorem states:
If energy is supplied to any system of conductors through N wires, the total power in 
the system is given by the algebraic sum of the readings of N wattmeters so arranged 
that each of the N wires contains one current coil, the corresponding potential coil 
being connected between that wire and some common point. If this common point is 
on one of the N wires, the measurement may be made by the use of N-1 Wattmeters.
I
A 
V
CA 
V
AB 
V
BC 
I
C 
I
B 
V
C
V
B
V
CA 
V
AB 
N
 
V
BC