CHAPTER 1: THREE-PHASE POWER MEASUREMENT REACTIVE ENERGY AND POWER FACTOR
EPM 2200 POWER METER – INSTRUCTION MANUAL 1–9
Figure 1-8: Energy Use and Demand 
As can be seen from this example, it is important to recognize the relationships 
between power, energy and demand in order to control loads effectively or to monitor 
use correctly.
1.6 Reactive Energy and Power Factor
The real power and energy measurements discussed in the previous section relate to 
the quantities that are most used in electrical systems. But it is often not sufficient to 
only measure real power and energy. Reactive power is a critical component of the 
total power picture because almost all real-life applications have an impact on 
reactive power. Reactive power and power factor concepts relate to both load and 
generation applications. However, this discussion will be limited to analysis of reactive 
power and power factor as they relate to loads. To simplify the discussion, generation 
will not be considered.
Real power (and energy) is the component of power that is the combination of the 
voltage and the value of corresponding current that is directly in phase with the 
voltage. However, in actual practice the total current is almost never in phase with the 
voltage. Since the current is not in phase with the voltage, it is necessary to consider 
both the inphase component and the component that is at quadrature (angularly 
rotated 90o or perpendicular) to the voltage. Figure 1.9 shows a single-phase voltage 
and current and breaks the current into its in-phase and quadrature components.
0
20
40
60
80
100
12345678
Intervals (15 mins.)
sruoh-ttawolik