CHAPTER 2: OVERVIEW AND SPECIFICATIONS HARDWARE OVERVIEW
EPM 2200 POWER METER – INSTRUCTION MANUAL 2–3
2.1.3 Measured Values
The following table lists the measured values available in real time, average, maximum,
and minimum.
2.1.4 Utility Peak Demand
The EPM 2200 provides user-configured Block (fixed) window, or Rolling window demand.
This feature allows you to set up a customized demand profile. Block window demand is
demand used over a user-configured demand period (usually 5, 15, or 30 minutes). Rolling
Table 2–2: EPM 2200 Accessory Order Codes
PL2200
*
*
DIN Bracket PL2200
ACC
DIN
EPM 2200 Meter DIN Mounting Bracket
Table 2–3: EPM 2200 Measured Values
Measured Values Real Time Average Maximum Minimum
Voltage L-N XXX
Voltage L-L XXX
Current per phase XXXX
Current Neutral X
Watts XXXX
VARs XXXX
VA XXXX
Power Factor (PF) XXXX
Positive watt-hours X
Negative watt-hours X
Net watt-hours X
Positive VAR-hours X
Negative VAR-hours X
Net VAR-hours X
VA-hours X
Frequency XXX
Voltage angles X
Current angles X
% of load bar X

Table of Contents