CHAPTER 2: OVERVIEW AND SPECIFICATIONS ACCURACY
EPM 2200 POWER METER – INSTRUCTION MANUAL 2–9
2.4 Accuracy
For 23 °C, 3 Phase balanced Wye or Delta load.
1 
For 2.5 element programmed units, degrade accuracy by an additional 0.5% of reading.
2 
For unbalanced voltage inputs where at least one crosses the 150V auto-scale threshold 
(for example, 120V/120V/208V system), degrade accuracy by additional 0.4%.
EPM 2200 accuracy meets the IEC62053-22 Accuracy Standards for 0.5% Class Meters. 
This standard is shown in the table below.
Note
In the table above:
I
n = Nominal (5A)
I
max = Full Scale
Parameter Accuracy Accuracy Input Range
Voltage L-N [V] 0.2% of reading
2
(69 to 480)V
Voltage L-L [V] 0.4% of reading (120 to 600)V
Current Phase [A] 0.2% of reading
1
(0.15 to 5)A
Current Neutral (calculated) 
[A]
2% of Full Scale
1
(0.15 to 5)A @ (45 to 65)Hz
Active Power Total [W] 0.5% of reading
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0.5 to 1) lag/lead PF
Active Energy Total [Wh] 0.5% of reading
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0.5 to 1) lag/lead PF
Reactive Power Total [VAR] 1.0% of reading
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0 to 0.8) lag/lead PF
Reactive Energy Total [VARh] 1.0% of reading
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0 to 0.8) lag/lead PF
Apparent Power Total [VA] 1.0% of reading
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0.5 to 1) lag/lead PF
Apparent Energy Total [VAh] 1.0% of reading
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0.5 to 1) lag/lead PF
Power Factor 1.0% of reading
1,2
(0.15 to 5)A @ (69 to 480)V @ +/- (0.5 to 1) lag/lead PF
Frequency +/- 0.01Hz (45 to 65)Hz
Load Bar +/- 1 segment
1
(0.005 to 6)A
Value of Current Power Factor Percentage Error Limits for
Meters of Class 0.5 S
0.01 I
n ≤ I < 0. 05 In 1 ±1.0
0.05 I
n ≤ I ≤ Imax 1 ±0.5
0.02 I
n ≤ I < 0.1 In 0.5 inductive
0.8 capacitive
±1.0
±1.0
0.1 I
n ≤ I ≤ Imax 0.5 inductive
0.8 capacitive
±0.6
±0.6
When specially requested by the 
user, from:
0.1 I
n ≤ I ≤ Imax
0.25 inductive
0.8 capacitive
±1.0
±1.0