4–6 EPM 2200 POWER METER – INSTRUCTION MANUAL
CONSIDERATIONS WHEN INSTALLING METERS CHAPTER 4: ELECTRICAL INSTALLATION
4.1.4 Voltage and Power Supply Connections
Voltage Inputs are connected to the back of the unit via a optional wire connectors. The
connectors accommodate up to AWG#12 / 2.5 mm wire.
Figure 4-4: Voltage Connection
4.1.5 Ground Connections
The EPM 2200 ground terminals ( ) should be connected directly to the installation's
protective earth ground. Use 2.5 mm wire for this connection.
4.1.6 Voltage Fuses
GE requires the use of fuses on each of the sense Voltages and on the control power.
Use a 0.1 Amp fuse on each voltage input.
Use a 3.0 Amp fuse on the Power Supply.
Power supply
inputs
Voltage
inputs
RS485 outputs
(do not place voltage
on these terminals!)