4–42 PQM POWER QUALITY METER – INSTRUCTION MANUAL
S4 ALARMS/CONTROL CHAPTER 4: PROGRAMMING
• UNDERVOLTAGE LEVEL: When the voltage on one, two, or three phases drops to or 
below this level, an undervoltage condition occurs. The number of phases required is 
determined by the 
PHASES REQUIRED FOR U/V OPERATION setpoint. To clear the 
undervoltage condition, the level must increase to 103% of the 
UNDERVOLTAGE 
LEVEL 
setting. For example, if the UNDERVOLTAGE LEVEL is set to 4000 V, the 
condition clears when the voltage in the appropriate phase(s) increases above 4120 V 
(4000 × 1.03). This hysteresis is implemented to avoid nuisance alarms due to voltage 
fluctuations.
• UNDERVOLTAGE DELAY: If the voltage drops to or below the 
UNDERVOLTAGE LEVEL 
setpoint value and remains this way for the time delay programmed in this setpoint, 
an undervoltage condition will occur.
• PHASES REQ’D FOR U/V OPERATION: Select the minimum number of phases on which 
the undervoltage condition must be detected before the selected output relay will 
operate. This setpoint is not visible if 
VT WIRING is set to SINGLE PHASE DIRECT.
• DETECT UNDERVOLTAGE BELOW 20V: If an indication is required for loss of voltage, 
select 
YES for this setpoint. If NO is selected and any one of the voltage inputs has less 
than 20 V applied, the undervoltage feature will be disabled.
• OVERVOLTAGE RELAY: Overvoltage can either be disabled, used as an alarm or as a 
process control. Set this setpoint to off if the feature is not required. Selecting alarm 
relay will cause the alarm relay to activate and display an alarm message whenever 
an overvoltage condition exists. Selecting auxiliary relay will cause the auxiliary relay 
to activate for an overvoltage condition but no message will be displayed. This is 
intended for process control.
• OVERVOLTAGE LEVEL: When the voltage on one, two, or three phases equals or 
exceeds the level determined with this setpoint, an overvoltage condition occurs. The 
number of phases required is determined by the 
PHASES REQUIRED FOR O/V 
OPERATION
 setpoint. To clear the overvoltage condition, the level must decrease to 
97% of the 
OVERVOLTAGE LEVEL setting. For example, if the OVERVOLTAGE LEVEL 
is set to 4200 V, the condition clears when the voltage in the appropriate phase(s) goes 
below 4074 V (4200 × 0.97). This hysteresis is implemented to avoid nuisance alarms 
due to voltage fluctuations.
• OVERVOLTAGE DELAY: If the voltage equals or exceeds the 
OVERVOLTAGE LEVEL 
setpoint value and remains this way for the time delay programmed in this setpoint, 
an overvoltage condition will occur.
• PHASES REQ’D FOR O/V OPERATION: Select the minimum number of phases on which 
the overvoltage condition must be detected before the selected output relay will 
operate. This setpoint is not visible if 
VT WIRING is set to SINGLE PHASE DIRECT.
• CURRENT UNBALANCE RELAY: Current unbalance is calculated as the maximum 
deviation from the average divided by the average three phase current. Current 
unbalance can either be disabled, used as an alarm or as a process control. Set this 
setpoint to off if the feature is not required. Selecting alarm relay will cause the alarm 
relay to activate and display an alarm message whenever a current unbalance 
condition exists. Selecting auxiliary relay will cause the auxiliary relay to activate for a 
current unbalance condition but no message will be displayed. This is intended for 
process control.
Courtesy of NationalSwitchgear.com