CHAPTER 4: PROGRAMMING S4 ALARMS/CONTROL
PQM POWER QUALITY METER – INSTRUCTION MANUAL 4–43
• CURRENT UNBALANCE LEVEL: When the current unbalance equals or exceeds this 
level, a current unbalance condition will occur. See chapter 5 for details on the method 
of calculation.
• CURRENT UNBALANCE DELAY: If the current unbalance equals or exceeds the 
CURRENT UNBALANCE LEVEL value for the time delay programmed in this setpoint, 
a current unbalance condition occurs.
• VOLTAGE UNBALANCE RELAY: Voltage unbalance is calculated as the maximum 
deviation from the average divided by the average three phase voltage. Voltage 
unbalance can either be disabled, used as an alarm or as a process control. Set this 
setpoint to off if the feature is not required. Selecting alarm relay will cause the alarm 
relay to activate and display an alarm message whenever a voltage unbalance 
condition exists. Selecting auxiliary relay will cause the auxiliary relay to activate for a 
voltage unbalance condition but no message will be displayed. This is intended for 
process control. 
• VOLTAGE UNBALANCE LEVEL: When the voltage unbalance equals or exceeds this 
level, a voltage unbalance condition occurs. See chapter 5 for details on the method of 
calculation.
• VOLTAGE UNBALANCE DELAY: If the voltage unbalance equals or exceeds the 
VOLTAGE UNBALANCE LEVEL setpoint value and remains this way for the time delay 
programmed in this setpoint, a voltage unbalance condition will occur.
• VOLTAGE PHASE REVERSAL: Under normal operating conditions, the PQM expects to 
see the voltages connected with a 1-2-3 or A-B-C sequence. If the voltages are 
connected with the wrong sequence, 2-1-3 or B-A-C, a voltage phase reversal 
condition will occur. A minimum of 20 V must be applied to the PQM on all voltage 
inputs before the phase reversal feature will operate.
A phase reversal condition is determined by looking at the phase angle at the 
occurrence of the peak sample of phase B voltage and subtracting it from the phase 
angle at the peak sample of phase A voltage (phase A angle - phase B angle). This 
angle is averaged over several cycles before deciding on the condition to avoid any 
false triggering of the feature. Only two phases are required to detect phase reversal 
because all phase reversal conditions can be covered without the use of the third 
phase. The angle to detect phase reversal will vary depending on the connection 
being used as described below.
Courtesy of NationalSwitchgear.com