CHAPTER 7: MODBUS COMMUNICATIONS MODBUS MEMORY MAP
PQM POWER QUALITY METER – INSTRUCTION MANUAL 7–27
POWER
02F0
02F1
3 Phase Real Power (high)
3 Phase Real Power (low)
--- --- 0.01 x kW F4 N/A
02F2
02F3
3 Phase Reactive Power (high)
3 Phase Reactive Power (low)
--- ---
0.01 x
kvar
F4 N/A
02F4
02F5
3 Phase Apparent Power (high)
3 Phase Apparent Power (low)
--- --- 0.01 x kVA F3 N/A
02F6 3 Phase Power Factor --- --- 0.01 x PF F2 N/A
02F7
02F8
Phase A Real Power (high)
Phase A Real Power (low)
--- --- 0.01 x kW F4 N/A
02F9
02FA
Phase A Reactive Power (high)
Phase A Reactive Power (low)
--- ---
0.01 x
kvar
F4 N/A
02FB
02FC
Phase A Apparent Power (high)
Phase A Apparent Power (low)
--- --- 0.01 x kVA F3 N/A
02FD Phase A Power Factor --- --- 0.01 x PF F2 N/A
02FE
02FF
Phase B Real Power (high)
Phase B Real Power (low)
-- --- 0.01 x kW F4 N/A
0300
0301
Phase B Reactive Power (high)
Phase B Reactive Power (low)
--- ---
0.01 x
kvar
F4 N/A
0302
0303
Phase B Apparent Power (high)
Phase B Apparent Power (low)
--- --- 0.01 x kVA F3 N/A
0304 Phase B Power Factor --- --- 0.01 x PF F2 N/A
0305
0306
Phase C Real Power (high)
Phase C Real Power (low)
--- --- 0.01 x kW F4 N/A
0307
0308
Phase C Reactive Power (high)
Phase C Reactive Power (low)
--- ---
0.01 x
kvar
F4 N/A
0309
030A
Phase C Apparent Power (high)
Phase C Apparent Power (low)
--- --- 0.01 x kVA F3 N/A
030B Phase C Power Factor --- --- 0.01 x PF F2 N/A
030C
030D
3 Phase Real Power - Minimum (high)
3 Phase Real Power - Minimum (low)
--- --- 0.01 x kW F4 N/A
030E
030F
3 Phase Reactive Power - Minimum (high)
3 Phase Reactive Power - Minimum (low)
--- ---
0.01 x
kvar
F4 N/A
0310
0311
3 Phase Apparent Power - Minimum (high)
3 Phase Apparent Power - Minimum (low)
--- --- 0.01 x kVA F3 N/A
0312 3 Phase Power Factor - Minimum --- --- 0.01 x PF F2 N/A
0313
0314
3 Phase Real Power - Maximum (high)
3 Phase Real Power - Maximum (low)
--- --- 0.01 x kW F4 N/A
0315
0316
3 Phase Reactive Power - Maximum (high)
3 Phase Reactive Power - Maximum (low)
--- ---
0.01 x
kvar
F4 N/A
0317
0318
3 Phase Apparent Power - Maximum (high)
3 Phase Apparent Power - Maximum (low)
--- --- 0.01 x kVA F3 N/A
0319 3 Phase Power Factor - Maximum --- --- 0.01 x PF F2 N/A
Table 7–10: PQM Memory Map (Sheet 11 of 55)
GROUP ADDR
(HEX)
DESCRIPTION RANGE STEP
VALUE
UNITS and
SCALE
FORMAT FACTORY
DEFAULT
Notes:* Data type depends on the Command Operation Code.** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents OFF.**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.****** Applicable to older revisions with VFD display only