7–48 PQM POWER QUALITY METER – INSTRUCTION MANUAL
MODBUS MEMORY MAP CHAPTER 7: MODBUS COMMUNICATIONS
EVENT
RECORD
0AD0 Total Number of Events Since Last Clear --- --- --- F1 0
0AD1 Event Record Last Cleared Time - Hrs./Min. --- --- --- F22 N/A
0AD2 Event Record Last Cleared Time - Seconds --- --- --- F23 N/A
0AD3 Event Record Last Cleared Date - Month/
Day
--- --- --- F24 N/A
0AD4 Event Record Last Cleared Date - Year --- --- --- F25 N/A
0AD5 Reserved
to
0ADF Reserved
0AE0 Record #N Event Number --- --- --- F1 N/A
0AE1 Record #N Event Cause --- --- --- F36 0 = NO EVENT
0AE2 Record #N Time - Hours/Minutes --- --- --- F22 N/A
0AE3 Record #N Time - Seconds --- --- --- F23 N/A
0AE4 Record #N Date - Month/Day --- --- --- F24 N/A
0AE5 Record #N Date - Year --- --- --- F25 N/A
0AE6 Record #N Switches and Relays States --- --- --- F111 N/A
0AE7 Record #N Ia --- --- A F1 N/A
0AE8 Record #N Ib --- --- A F1 N/A
0AE9 Record #N Ic --- --- A F1 N/A
0AEA Record #N In --- --- A F1 N/A
0AEB Record #N I Unbalance --- --- 0.1 x% F1 N/A
0AEC
0AED
Record #N Van (high)
Record #N Van (low)
--- --- V F3 N/A
0AEE
0AEF
Record #N Vbn (high)
Record #N Vbn (low)
--- --- V F3 N/A
0AF0
0AF1
Record #N Vcn (high)
Record #N Vcn (low)
--- --- V F3 N/A
0AF2
0AF3
Record #N Vab (high)
Record #N Vab (low)
--- --- V F3 N/A
0AF4
0AF5
Record #N Vbc (high)
Record #N Vbc (low)
--- --- V F3 N/A
0AF6
0AF7
Record #N Vca (high)
Record #N Vca (low)
--- --- V F3 N/A
0AF8 Record #N V Unbalance --- --- 0.1 x% F1 N/A
0AF9
0AFA
Record #N Pa (high)
Record #N Pa (low)
--- --- 0.01 x kW F4 N/A
0AFB
0AFC
Record #N Qa (high)
Record #N Qa (low)
--- ---
0.01 x
kvar
F4 N/A
0AFD
0AFE
Record #N Sa (high)
Record #N Sa (low)
--- --- 0.01 x kVA F3 N/A
Table 7–10: PQM Memory Map (Sheet 32 of 55)
GROUP ADDR
(HEX)
DESCRIPTION RANGE STEP
VALUE
UNITS and
SCALE
FORMAT FACTORY
DEFAULT
Notes:* Data type depends on the Command Operation Code.** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents OFF.**** Minimum Setpoint value represents “OFF.
***** Maximum Setpoint value represents “UNLIMITED”.****** Applicable to older revisions with VFD display only
Courtesy of NationalSwitchgear.com