CHAPTER 7: MODBUS COMMUNICATIONS MODBUS MEMORY MAP
PQM POWER QUALITY METER – INSTRUCTION MANUAL 7–55
ANALOG
OUTPUT 1
1060 Analog Output 1 Main Type 0 to 59 1 --- F14 5=Avg Ph Current
1061 Analog Output 1 Main Min Value See Analog Output Range Table on page –92 0
1062 Analog Output 1 Main Max Value See Analog Output Range Table on page –92 0
1063 Analog Output 1 Alternate Type 0 to 59 1 --- F14 0=NOT USED
1064 Analog Output 1 Alternate Min Value See Analog Output Range Table on page –92 0
1065 Analog Output 1 Alternate Max Value See Analog Output Range Table on page –92 0
1066 Reserved
1067 Analog Output 1 Serial Value 1 --- F2 0
ANALOG
OUTPUT 2
1068 Analog Output 2 Main Type 0 to 59 1 --- F14 18=3Ph Real
Power
1069 Analog Output 2 Main Min Value See Analog Output Range Table on page –92 0
106A Analog Output 2 Main Max Value See Analog Output Range Table on page –92 0
106B Analog Output 2 Alternate Type 0 to 59 1 --- F14 0=NOT USED
106C Analog Output 2 Alternate Min Value See Analog Output Range Table on page –92 0
106D Analog Output 2 Alternate Max Value See Analog Output Range Table on page –92 0
106E Reserved
106F Analog Output 2 Serial Value 1 --- F2 0
ANALOG
OUTPUT 3
1070 Analog Output 3 Main Type 0 to 59 1 --- F14 19=3Ph Reactive
Pwr
1071 Analog Output 3 Main Min Value See Analog Output Range Table on page –92
1072 Analog Output 3 Main Max Value See Analog Output Range Table on page –92
1073 Analog Output 3 Alternate Type 0 to 59 1 --- F14 0=NOT USED
1074 Analog Output 3 Alternate Min Value See Analog Output Range Table on page –92
1075 Analog Output 3 Alternate Max Value See Analog Output Range Table on page –92
1076 Reserved
1077 Analog Output 3 Serial Value 1 --- F2 0
ANALOG
OUTPUT 4
1078 Analog Output 4 Main Type 0 to 59 1 --- F14 17=3Ph Power
Factor
1079 Analog Output 4 Main Min Value See Analog Output Range Table on page –92
107A Analog Output 4 Main Max Value See Analog Output Range Table on page –92
107B Analog Output 4 Alternate Type 0 to 59 1 --- F14 0=NOT USED
107C Analog Output 4 Alternate Min Value See Analog Output Range Table on page –92
107D Analog Output 4 Alternate Max Value See Analog Output Range Table on page –92
107E Reserved
107F Analog Output 4 Serial Value 1 --- F2 0
Table 7–10: PQM Memory Map (Sheet 39 of 55)
GROUP ADDR
(HEX)
DESCRIPTION RANGE STEP
VALUE
UNITS and
SCALE
FORMAT FACTORY
DEFAULT
Notes:* Data type depends on the Command Operation Code.** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”.**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.****** Applicable to older revisions with VFD display only