7–56 PQM POWER QUALITY METER – INSTRUCTION MANUAL
MODBUS MEMORY MAP CHAPTER 7: MODBUS COMMUNICATIONS
ANALOG
INPUT
1080 Analog Input Main/Alt Select Relay 0 to 3 1 --- F19 0=OFF
1081 Analog In Main Name 1
st
and 2
nd
char. --- --- ASCII F10 ““
1082 Analog In Main Name 3
rd
and 4
th
char. --- --- ASCII F10 “MA
1083 Analog In Main Name 5
th
and 6
th
char. --- --- ASCII F10 IN”
1084 Analog In Main Name 7
th
and 8
th
char. --- --- ASCII F10 A
1085 Analog In Main Name 9
th
and 10
th
char. -- -- ASCII F10 NA
1086 Analog In Main Name 11
th
and 12
th
char. -- -- ASCII F10 LO
1087 Analog In Main Name 13
th
and 14
th
char. --- --- ASCII F10 G
1088 Analog In Main Name 15
h
and 16
th
char. ---- ---- ASCII F10 IN”
1089 Analog In Main Name 17
th
and 18
th
char. --- --- ASCII F10 “PU”
108A Analog In Main Name 19
th
and 20
th
char. --- --- ASCII F10 T
108B Analog In Main Units 1
st
and 2
nd
char. --- --- ASCII F10 U
108C Analog In Main Units 3
rd
and 4
th
char. --- --- ASCII F10 “ni”
108D Analog In Main Units 5
th
and 6
th
char. --- --- ASCII F10 “ts”
108E Analog In Main Units 7
th
and 8
th
char. --- --- ASCII F10
108F Analog In Main Units 9
th
and 10
th
char. --- --- ASCII F10 ““
1090 Analog Input Main 4 mA Value 0 to 65000 1 --- F1 0
1091 Analog Input Main 20 mA Value 0 to 65000 1 --- F1 0
1092 Analog Input Main Relay 0 to 4 1 --- F29 0=OFF
1093 Analog Input Main Level 0 to 65000 1 --- F1 0
1094 Analog Input Main Delay 5 to 6000 5 0.1 x s F1 100=10.0 s
1095 Reserved
1096 Reserved
1097 Reserved
1098 Analog In Alt Name 1
st
and 2
nd
char. --- --- ASCII F10 ““
1099 Analog In Alt Name 3
rd
and 4
th
char. --- --- ASCII F10 AL”
109A Analog In Alt Name 5
th
and 6
th
char. --- --- ASCII F10 T
109B Analog In Alt Name 7
th
and 8
th
char. --- --- ASCII F10 A
109C Analog In Alt Name 9
th
and 10
th
char. -- -- ASCII F10 NA
109D Analog In Alt Name 11
th
and 12
th
char. -- -- ASCII F10 LO
109E Analog In Alt Name 13
th
and 14
th
char. --- --- ASCII F10 G
109F Analog In Alt Name 15
h
and 16
th
char. ---- ---- ASCII F10 IN”
10A0 Analog In Alt Name 17
th
and 18
th
char. --- --- ASCII F10 “PU”
10A1 Analog In Alt Name 19
th
and 20
th
char. --- --- ASCII F10 T
10A2 Analog In Alt Units 1
st
and 2
nd
char. --- --- ASCII F10 U
10A3 Analog In Alt Units 3
rd
and 4
th
char. --- --- ASCII F10 “ni”
10A4 Analog In Alt Units 5
th
and 6
th
char. --- --- ASCII F10 “ts”
10A5 Analog In Alt Units 7
th
and 8
th
char. --- --- ASCII F10
10A6 Analog In Alt Units 9
th
and 10
th
char. --- --- ASCII F10 ““
10A7 Analog Input Alt 4 mA Value 0 to 65000 1 --- F1 0
10A8 Analog Input Alt 20 mA Value 0 to 65000 1 --- F1 0
Table 7–10: PQM Memory Map (Sheet 40 of 55)
GROUP ADDR
(HEX)
DESCRIPTION RANGE STEP
VALUE
UNITS and
SCALE
FORMAT FACTORY
DEFAULT
Notes:* Data type depends on the Command Operation Code.** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents OFF.**** Minimum Setpoint value represents “OFF.
***** Maximum Setpoint value represents “UNLIMITED”.****** Applicable to older revisions with VFD display only