8–12 PQM POWER QUALITY METER – INSTRUCTION MANUAL
DNP 3.0 PROTOCOL CHAPTER 8: DNP COMMUNICATIONS
12 0244 Neutral Current
1000ths of
nominal
20 units F1 1
13 0245 Current Unbalance
tenths of 1
percent
10 units F1 2
14 0280 Voltage Van
1000ths of
nominal V
10 units F3 1
15 0282 Voltage Vbn
1000ths of
nominal V
10 units F3 1
16 0284 Voltage Vcn
1000ths of
nominal V
10 units F3 1
17 0286 Average Phase Voltage
1000ths of
nominal V
10 units F3 1
18 0288 Voltage Vab
1000ths of
nominal V
10 units F3 1
19 028A Voltage Vbc
1000ths of
nominal V
10 units F3 1
20 028C Voltage Vca
1000ths of
nominal V
10 units F3 1
21 028E Average Line Voltage
1000ths of
nominal
10 units F3 1
22 0290 Voltage Unbalance 0.1 x % 10 units F1 2
23 02F0 3 Phase Real Power
1000ths of
nominal VA
20 units F4 2
24 02F2 3 Phase Reactive Power
1000ths of
nominal VA
20 units F4 2
25 02F4
3 Phase Apparent
Power
1000ths of
nominal VA
20 units F3 2
26 02F6 3 Phase Power Factor % 10 units F2 2
27 02F7 Phase A Real Power
1000ths of
nominal
20 units F4 3
28 02F9 Phase A Reactive Power
1000ths of
nominal
20 units F4 3
29 02FB
Phase A Apparent
Power
1000ths of
nominal
20 units F3 3
30 02FD Phase A Power Factor % 10 units F2 3
Table 8–4: Point List for Analog Input/Output Change (Sheet 2 of 9)
POINT MOBUS
REG
DESCRIPTION UNIT /
VALUE
DEADBAND FORMAT
CODE
EVENT
CLASS
ASSIGNED
TO
see footnote explanations at the end of the table