CHAPTER 8: DNP COMMUNICATIONS DNP 3.0 PROTOCOL
PQM POWER QUALITY METER – INSTRUCTION MANUAL 8–13
31 02FE Phase B Real Power
1000ths of
nominal
20 units F4 3
32 0300 Phase B Reactive Power
1000ths of
nominal
20 units F4 3
33 0302
Phase B Apparent
Power
1000ths of
nominal
20 units F3 3
34 0304 Phase B Power Factor % 10 units F2 3
35 0305 Phase C Real Power
1000ths of
nominal
20 units F4 3
36 0307 Phase C Reactive Power
1000ths of
nominal
20 units F4 3
37 0309
Phase C Apparent
Power
1000ths of
nominal
20 units F3 3
38 030B Phase C Power Factor % 10 units F2 3
39 0400
Phase A Current
Demand
1000ths of
nominal
20 units F1 3
40 0401
Phase B Current
Demand
1000ths of
nominal
20 units F1 3
41 0402
Phase C Current
Demand
1000ths of
nominal
20 units F1 3
42 0403
Neutral Current
Demand
1000ths of
nominal
20 units F1 3
43 0404
3 Phase Real Power
Demand
1000ths of
nominal
20 units F4 3
44 0406
3 Phase React Power
Demand
1000ths of
nominal
20 units F4 3
45 0408
3 Phase Apparent
Power Demand
1000ths of
nominal
20 units F3 3
46 0440 Frequency 0.01x Hz .05 Hz F1 1
47 0458
Main/Alternate Analog
Input
Unit varies
-- 32 bits
10 F3 2
48 0470 Ia Crest Factor 0.001 x CF 50 F1 -
49 0471 Ib Crest Factor 0.001 x CF 50 F1 -
50 0472 Ic Crest Factor 0.001 x CF 50 F1 -
Table 8–4: Point List for Analog Input/Output Change (Sheet 3 of 9)
POINT MOBUS
REG
DESCRIPTION UNIT /
VALUE
DEADBAND FORMAT
CODE
EVENT
CLASS
ASSIGNED
TO
see footnote explanations at the end of the table